Deice Operation Time Chart
·
Compressor frequency is set at 40Hz when the deice operation starting signal is generated.
·
120 seconds later deice operation starting signal is generated, indoor fan, outdoor fan, 4-way valve are turned off and
compressor operates at 61Hz for 30 seconds. (Deice operation starts)
·
During deice operation, the compressor operating frequency is set at 85Hz.
·
Deice will end when the outdoor heat exchanger temperature rises to 13°C or after 11 min 30sec.
24
CS-MVG103KE / CU-MVG153KE