9 Operation Details (PROTECTION)
9.1. PROTECTION CONTROL FOR ALL OPERATIONS
1. Time Delay Safety Control
·
The compressor is not restarted for 3 minutes after stop of compressor.
2. 30 Second Forced Operation
·
Once the compressor is ON, it will not turn OFF for 30 seconds. However, it is turned off by remote control or Automatic
switch.
3. Total Running Current Control
·
When the outdoor unit total running current (AC) exceeds l1, the frequency is lowered by 1 rank. If l1 is not exceeded for
30 seconds, the frequency is highered by 1 rank at one time. If the outdoor unit total running current exceeds l2, the
compressor is immediately stopped for 3 minutes.
< Cooling, Soft Dry set value >
Note:
Zone A will be used 30 minutes after operation starts.
< Heating set value >
35
CS-MVG103KE / CU-MVG153KE