9.3. PROTECTION CONTROL FOR HEATING OPERATION
1. Intake Air Temperature Control
·
When the intake air temperature is 10°C or above and remote control setting fan speed is less than Medium, the
compressor operates at 92Hz.
2. High Pressure Control
·
The compressor operating frequency is regulated in accordance to the indoor heat exchanger temperature.
40
CS-MVG103KE / CU-MVG153KE