8.4. COOLING OPERATION
8.4.1. Room Temperature Control
1. When the remote control setting temperature is less than 24°C.
Refer to8.3.2. Compressor Operation Frequency
2. When the remote control setting temperature is 24°C and above.
Refer to8.3.1. Compressor Operation Frequency
·
Thermostat OFF temperature = Thermostat ON temperature.
·
The Comp. Operation Frequency Command can be changed every 30 seconds.
·
30 minutes from the start of the operation, the compressor is operating at Fc max.
·
The Thermostat OFF when the intake air temperature reaches 1°C below internal setting temperature and continues for 3
minutes.
·
When the Thermostat of both Indoor Units OFF, the Compressor stops.
·
When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
·
When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation.
·
When the compressor stops, the outdoor fan motor stops 30 seconds later.