4. Power Transistor Overheating Prevention Control
·
When the power transistor temperature rises to 110°C, the OLP goes into operation and compressor stops immediately. The
compressor is restarted when the power transistor temperature decreases to 95°C after 3 minutes (Time Delay Safety
Control).
5. Compressor Overheating Prevention Control
·
When the temperature of compressor rises to 105°C, the frequency is reduced as shown in diagram below. When the
temperature rises to 112° or above, the compressor stops. The compressor will start operating at low frequency when the
temperature falls to 112°C and resume to normal condition when the temperature falls to 94°C.
36
CS-MVG103KE / CU-MVG153KE