Setting temp °C T1 T2 T3
Note:
Base temperature for T1 is 29 °C
Base temperature for T2 is 27 °C
Base temperature for T3 is 21 °C
18 and below +10 +8 -5
19 - 22 +8 +7 -7
23 - 26 +7 +6 -7
27 and above +6 +5 -8
·
When the operation mode is changed over, the value for t1, t2 and t3 are shifted as follows:
Cooling/Soft dry → Heating: -2°C
Heating → Cooling/Soft dry: +2°C
·
When the indoor intake air temperature is lower than 16°C, heating operation is immediately started.
·
When the outdoor air temperature is more than 25°C, and the intake air temperature is over 16°C, cooling operation is
immediately started.
·
The operation mode is judged every 3 hours.
8.8.1. Temperature Shift
·
When the operation mode (Heating, Cooling or Soft Dry) is decided, the internal setting temperature will shift as shown below: