11. Outdoor Air Temperature Control
·
The compressor operating frequency is regulated in accordance to the outdoor air temperature.
< Cooling, Soft Dry >
< Heating >
12. 2 way valve control ( Protection of compressor )
·
When the 2 way valve is ON at
a. 15 seconds later after the compressor started operation.
( ON time of 2 way valve is 45 seconds. )
b. During Deice operation.
·
The 2 way valve is OFF at during normal operation.
38
CS-MVG103KE / CU-MVG153KE