5-53
5
P13 Alarm Valve Open
Error Detection Method
Error Diagnosis
1.
2.
Detection is performed only in the test run. When once detected or the test run finished without any error,
the second detection will not be done.
In case of forgetting to open a valve, P04 (high-pressure switch operational alarm) is occasionally preceded due to the
following conditions.
The status of small temperature change of the operating indoor unit continues for the first 7 minutes since the
cooling test run has started.
•
1-1
2-1
Yes
No
1 Service
valve
Open the service
valve
2-1
2
Adjustment
to
refrigerant
change
3
Blockage
in
refrigerant
circuit
3-1
Avoid clogging
3-2
Yes
No
Are the tubes clogged?
Not additional refrigerant charged
3-1
Yes
No
Additional
refrigerant charge
3-2
3-3
Replace the
electronic control
valve
Yes
No
Is the outdoor unit’s electronic control valve operating correctly?
(Check for debris clogging the electronic control valve, a problem
with the electronical coil and/or the control PC board.)
3-3 As the second detection is not done, restart and see what happens if there is no error.
Service valve inside the outdoor unit closed
SM830231-02Singleī™€ę¬§å·ž.indb53SM830231-02Singleī™€ę¬§å·ž.indb53 2014/09/1115:44:192014/09/1115:44:19

Table of Contents

Other manuals for Panasonic CZ-KPY3A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CZ-KPY3A series and is the answer not in the manual?

Panasonic CZ-KPY3A series Specifications

General IconGeneral
BrandPanasonic
ModelCZ-KPY3A series
CategoryAir Conditioner
LanguageEnglish

Related product manuals