1 System
configuration
Is the indoor EEPROM setting, item code 0B, on the indoor unit’s
control PC board set to 0001?
2-1
After correcting the
setting, 3-1
4-1
Yes
No
2 Indoor unit’s
EEPROM
setting
P14 O2 Sensor Detect
Error Detection Method
Error Diagnosis
It is judged an error whenever the outdoor unit receives the signal ā€œO2 Alarm Occurredā€ from the indoor unit.
•
With the indoor unit’s EEPROM setting (item code 0B) set to 0001, the EXCT input was shorted.
•
1.
2.
Is an O2 sensor being used?
Correct wiring
4-1
Yes
No
Is the indoor EXCT socket (wire) shorted?3-1
3
4
Indoor EXCT
wiring
4-3
4-2
Yes
No
Is the alarm triggered if the indoor EXCT socket (wire) is
disconnected, and the power is reset?
Since there is no error, see what happens.
4-1
4-2
4-3 Indoor unit control PC board error replace PC board.
Indoor unit’s
control
PC board
SM830231-02Singleī™€ę¬§å·ž.indb54SM830231-02Singleī™€ę¬§å·ž.indb54 2014/09/1115:44:192014/09/1115:44:19

Table of Contents

Other manuals for Panasonic CZ-KPY3A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CZ-KPY3A series and is the answer not in the manual?

Panasonic CZ-KPY3A series Specifications

General IconGeneral
BrandPanasonic
ModelCZ-KPY3A series
CategoryAir Conditioner
LanguageEnglish

Related product manuals