5-54
5
1-1
3-1
2-1
Yes
No
1 System
configuration
Is the indoor EEPROM setting, item code 0B, on the indoor unitās
control PC board set to 0001?
2-1
After correcting the
setting, 3-1
4-1
Yes
No
2 Indoor unitās
EEPROM
setting
P14 O2 Sensor Detect
Error Detection Method
Error Diagnosis
It is judged an error whenever the outdoor unit receives the signal āO2 Alarm Occurredā from the indoor unit.
ā¢
With the indoor unitās EEPROM setting (item code 0B) set to 0001, the EXCT input was shorted.
ā¢
1.
2.
Is an O2 sensor being used?
Correct wiring
4-1
Yes
No
Is the indoor EXCT socket (wire) shorted?3-1
3
4
Indoor EXCT
wiring
4-3
4-2
Yes
No
Is the alarm triggered if the indoor EXCT socket (wire) is
disconnected, and the power is reset?
Since there is no error, see what happens.
4-1
4-2
4-3 Indoor unit control PC board error replace PC board.
Indoor unitās
control
PC board
SM830231-02īSingleī꬧å·.indbīīī54SM830231-02īSingleī꬧å·.indbīīī54 2014/09/11īīī15:44:192014/09/11īīī15:44:19