7-8
7
Item code Item
Setting data
noitpircseD.oN
(1B)
Forced thermostat ON
time
0000 5 minutes
0001 4 minutes
Temperature shift for
cooling/heating change
in auto heat/cool mode
0001 ± 1°C
0002 ± 2°C
0003 ± 3°C
0007 ± 7°C
(Upper limit)
(Lower limit)
Change to remote
control temperature
setting range
Cooling
0018 18°C (Lower limit at shipment)
0019 19°C
0029 29°C
0030 30°C (Upper limit at shipment)
(Upper limit)
(Lower limit)
Heating
0016 16°C (Lower limit at shipment)
0017 17°C
0029 29°C
0030 30°C (Upper limit at shipment)
(Upper limit)
(Lower limit)
Drying
0018 18°C (Lower limit at shipment)
0019 19°C
0029 29°C
0030 30°C (Upper limit at shipment)
(Upper limit)
(Lower limit)
Auto heat/cool
0017 17°C (Lower limit at shipment)
0018 18°C
0026 26°C
0027 27°C (Upper limit at shipment)
Humidifier operation
0000 Normal
0001 Ignore heat exchanger temperature conditions.
Filter (CN70) input
switching
0000 Filter input (differential pressure switch input)
0001 Alarm input (for trouble input about air cleaner or similar device)
0002
Humidifier input (Operates linked with drain pump when
humidifier is ON.)
Indoor unit electronic
control valve
0000 Present (Setting at shipment)
0002 None
T10 terminal switching
0000
Normal (Used as optional relay PCB or JEMA standard HA
terminal.)
0001 Used for OFF reminder
0002 Fire prevention input