7-9
7
Item code Item
Setting data
No. Description
Automatic drain pump
operation
0000 No forced operation
0001 Forced operation for 1 minute
0060
Continuous operation
Ventilation fan operation
0000
None
0001 Ventilation fan operated by remote controller.
Wired remote controller
sensor
0000 Not used. (Body sensor is used.)
0001
Remote control sensor is used.
āOperation change control in
progressā display
0000
Normal (displayed)
0001
Not displayed
OFF reminder function for
when weekly timer is used
0000 None
0001
Only stop time setting is enabled.
Heat exchanger temperature
for cold air discharge
(Heat exchanger control
point for control to prevent
cold air)
Control temperature 8°C
Control temperature 9°C
0008
0009
0025 Control temperature 25°C
0026 Control temperature 26°C
Fan output switching
0000 Output linked with fan. (ON when indoor unit fan is operating.)
0001 Fan mode operation output
Drain pump delayed start
time
0000 No delayed start
0001 1 minute delayed start
0002 2 minutes delayed start
0058 58 minutes delayed start
0059 59 minutes delayed start
0060 60 minutes delayed start
Humidifier setting
0000 Humidifier output OFF. Drain pump stopped.
0001 Humidifier output ON. Drain pump operates.
0002
Humidifier output ON. Drain pump operates for 1 minute when
total humidifier operating time reaches 60 minutes.
0003 Humidifier output ON. Drain pump stopped.
Flap operation mode
0000 Standard setting
0001
Draft reduction mode (Flap lower-limit position is shifted
upwards.)
Flap swing mode
0000
Smudging reduction mode (Flap swing upper-limit position is
shifted downwards.)
0001 Normal mode
0002
Draft reduction mode (Flap swing lower-limit position is shifted
upwards.)
Sec7.inddīīī7 2012/02/28īīī15:07:23
SM830231-02īSingleī꬧å·.indbīīī9SM830231-02īSingleī꬧å·.indbīīī9 2014/09/09īīī21:19:302014/09/09īīī21:19:30