7-10
7
Item code Item
Setting data
No. Description
Fan tap setting
(Fan tap change in order
to prevent drop in air
discharge caused by filter
installation)
DC fan tap
operating mode
Purpose
0000 Standard Standard (setting at shipment)
0001
High ceiling use High ceiling setting 1 (with standard panel)
For low static-
pressure filter
Ultra long-life filter, oil guard panel, ammonia
deodorizing filter, optical regenerative
deodorizing filter
0003
High ceiling use High ceiling setting 2 (with standard panel)
For low static-
pressure filter
(Antibacterial) high-performance filter (90%)
(Antibacterial) high-performance filter (65%)
Air-cleaning unit, air-cleaning unit + optical
regenerative deodorizing filter, deodorant
(activated charcoal) filter
For air-blocking
material
For 3-Way discharge, when discharge duct is
connected
0006
For air-blocking
material
For 2-Way discharge
Humidifier ON time
(ON time per 60 seconds)
0000 No humidifier output
0001 1 second.
0002 2 seconds.
0058 58 seconds.
0059 59 seconds.
0060 Continuously ON
Timer function change
prohibit
0000 Function disabled
0001 Function enabled
Smudging control 0000 No smudging control
Sec7.indd8 2012/02/2815:07:24
SM830231-02Singleī™€ę¬§å·ž.indb10SM830231-02Singleī™€ę¬§å·ž.indb10 2014/09/0921:19:302014/09/0921:19:30

Table of Contents

Other manuals for Panasonic CZ-KPY3A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CZ-KPY3A series and is the answer not in the manual?

Panasonic CZ-KPY3A series Specifications

General IconGeneral
BrandPanasonic
ModelCZ-KPY3A series
CategoryAir Conditioner
LanguageEnglish

Related product manuals