B19
B18
English
3. System Conguration and Wiring
Wiring of the Main Circuit
(Terminal block type)
F-frame, 200 V type
•Wiringshouldbeperformedbyaspecialistoranauthorizedpersonnel.
•Donotturnonthepoweruntilthewiringiscompleted.
•Nevertouchtheterminaltowhichhighvoltageisapplied.Thereisariskofelectric
shock.
• Tips on Wiring
1)Takeoffthecoverxingscrews,anddetachtheterminalcover.
2)Makewiring
Useclamptypeterminalsofroundshapewithinsulationcoverforwiringtotheter-
minalblock.Forcablediameterandsize,referto“DriverandListofApplicablePe-
ripheralEquipments”(P.B14).
Tightentheterminalblockscrewwithatorquebetween1.0and1.7N
m.
3)Attachtheterminalcover,andxwithscrews.
TightenthescrewsecuringthecoverwithatorquewrittenonP.B15.
Motor
Varistor
DC
24 V
L1
U
V
W
E
L2
L3
L1C
L2C
B1
B3
B2
NC
U
V
W
Check the name plate of the driver for power
specifications.
Provide a residual current device. The residual current
device to be the one designed for "Inverter" and is
equipped with countermeasures for harmonics.
Provide a circuit breaker.
Make sure to provide a noise filter.
Provide coil surge suppression units to the coil of the
Magnetic Contactor recommended by manufacturer.
Never start/stop the motor with this Magnetic
Contactor.
Provide an AC Reactor.
Don't disconnect the short bar between B1 and B2.
Disconnect this only when an external regenerative
register is used.
Do not connect anything to NC.
Match the colors of the motor lead wires to those of the
corresponding motor output terminals (U,V,W).
Avoid shorting and grounding.
Don't connect the main power.
Earth-ground this.
To prevent electric shock, be sure to connect the ground
terminal ( ) of the driver, and the ground terminal
(ground plate) of the control panel.
The ground terminal ( ) must not be shared with other
equipment.
Two ground terminals are provided.
Don't connect the earth cable to other inserting slot,
nor make them touch.
Compose a duplex Brake Control Circuit so that the
brake can also be activated by an external immediate
stop signal.
The holding Brake has no polarity.
For the capacity of the holding brake and how to use it,
refer to P.B43, "Specifications of Built-in Holding Brake".
Provide a varistor.
Connect a 10 A fuse in series with the varistor.
Ground resistance: 100 Ω max.
For applicable wire, refer to P.B14.
DC power
supply
for brake
Fuse (125 V 10 A)
Red
Black
Green
White
MCCB
Power
supply
NF MC LRCD
External regenerative
resistor
* These colors
are used for
optional cable.
3. System Conguration and Wiring
Wiring method to connector
•
FollowtheproceduresbelowforthewiringconnectiontotheConnector
XA
,
XB
and
XC
.
How to connect
1.Peelofftheinsulationcoverofthecable.
•Forsinglewire(Pleaseobeythelengthingure.)
•Forstrandedwires(ferrulesmustbeusedasillustratedbelow).
Example:
Ferrules with plastic insulating sleeve (AI series, Phoenix Contact, Ltd.)
1)Peeloffthesheathsothattheconductorportionofthecablewillprotrudefrom
thetipoftheferrule.(Itshouldprotrude
1mmormorefromtheferrule.)
2)Insertthecableintotheferruleandcrimp
itwithanappropriatecrimpingtool.
3)Aftercrimping,cutoffthecableconductor
portionprotrudingfrom the ferrule. (The
allowableprotrudinglength aftercutting
shouldbe0to0.5mm.)
•PartNo.ofthecrimpingtool:
CRIMPFOXU-D66(1204436)
AvailablefromPhoenixContact,Ltd.
Examples: Nylon-insulated ferrule (NTUB series, J.S.T. Mfg. Co., Ltd.)

Vinyl-insulated ferrule (VTUB series, J.S.T. Mfg. Co., Ltd.)
1)Peeloffthe sheathofthecableconduc-
tor portiontothelengthequalto that of
sheathontheferrule.
2)Insertthecableintotheferruleandcrimp
itwithanappropriatecrimpingtool.
•PartNo.ofthecrimpingtool:YNT-1614
AvailablefromJ.S.T.Mfg.Co.,Ltd
<Cables Compatible with Connector>
ConductorSize AWG18to12
SheathOutline φ2.1toφ4.2mm
<Recommended Connector Bar Terminal>
ConductorSize AWG18
TerminalModelNumber AI0.75-8GY(PhoenixContact,Ltd.)
ConductorSize AWG16to14
TerminalModelNumber VTUB-2orNTUB-2(J.S.T.Mfg.Co.,Ltd)
Caution
•Whenpeeling offthe sheathofthe cable,takecare nottodamage
otherportions.
•Whencrimping the ferrule, sufciently check the status of theferrule
andcable.Iftheconductorsofthecablestickoutfromtheinsulation
coverorprotrudeexcessivelyfromthetipoftheferrule,accidentssuch
asanelectricshockandrefromashortcircuitmayresult.
8 to 9 mm
A
A>B
1 mm or more
B
A
AB AB+C
B C