Alarm connection
When a signal output from the other device is supplied to the Alarm input 1 to 9 terminals (pin nos. 1 - 9), recording or an alarm
action will be performed in accordance with the settings.
When an alarm device such as a buzzer, a lamp, etc., is installed outside, connect them to the Alarm output terminal (pin no. 21).
Time and polarities of the ALARM/CONTROL connector
Terminal Activation time Remarks
Alarm input 100 ms or more N.O.: L active
N.C.: H active
Network error output At an error occurrence until the period selected for "Error
output duration" has passed*
L active
Alarm reset input 100 ms or more L active
Face matching output The set time on the setup menu L active
HDD error output At an error occurrence until the period selected for "Error
output duration" has passed*
L active
Camera error output At an error occurrence until the period selected for "Error
output duration" has passed* or the camera reset
L active
Recorder error output At an error occurrence until the period selected for "Error
output duration" has passed*
L active
Recording error output At an error occurrence until the period selected for "Error
output duration" has passed*
L active
Time adjustment signal input Input: 100 ms or more L active
Alarm output The set time on the setup menu L active
* The error output duration is configured on the "Advanced setup" menu - the "Maintenance" page of the setup menu.
(☞ Page 71)
Note:
• During"Lactive(Lowactive)",thelogicwillbeimplementedwhenthevoltagelevelofsignalislow.
• During"Hactive(Highactive)",thelogicwillbeimplementedwhenthevoltagelevelofsignalishigh.