- 27 -
Recognition) if a tamper or wire fault occurs on a
bypassed zone.
8.4 KEYPAD PANIC OPTIONS
Sections [506], [510], [514], [518] - Options [1] to [6]
As the control panel can enable Keypad Panic
Options for each individual partition, select the
section that corresponds to the desired partition and
set options [1] through [6] on/off to obtain the desired
options as described below.
Option [1] ON – PANIC 1
Pressing the [1] & [3] keys simultaneously on the
keypad for 2 seconds will generate a silent or audible
alarm as defined by option [4].
Option [2] ON – PANIC 2
Pressing the [4] & [6] keys simultaneously on the
keypad for 2 seconds will generate a silent or audible
alarm as defined by option [5].
Option [3] ON – PANIC 3
Pressing the [7] & [9] keys simultaneously on the
keypad for 2 seconds will generate a silent or audible
alarm as defined by option [6].
Option [4] ON = Panic 1 – Silent
OFF = Panic 1 – Audible
Option [5] ON = Panic 2 – Silent
OFF = Panic 2 – Audible
Option [6] ON = Panic 3 – Silent
OFF = Panic 3 – Pulsed (Fire)
Silent operation:
The control panel emits a single confirmation beep
and transmits the appropriate report code (see
section 9.2.5) to the central station.
Audible operation:
The alarm output (bell/siren) activates until a user
cancels the alarm with a valid User Access Code or
when the Bell Cut-Off Timer elapses (see section 8.2).
Fire operation:
Same as audible operation, except that the
bell/siren output will be pulsed as shown in figure
5.3 on page 17.