- 44 -
screen. If any missing modules are detected (i.e.
detector removed from the bus) during this scan, the
control panel will erase the module’s serial number,
removing the module from the control panel’s
memory.
12.15 POWER SAVE MODE
Section [504]: Options [4]
When the control panel is running on the back-up
battery (no AC), the control panel can set all keypads
into a “sleep mode”. In “sleep mode” the keypad’s
backlight and LEDs will be disabled and the LCD
screen will no longer display any messages until a key
is pressed, an alarm occurs or during an entry delay.
12.16 AUTO TROUBLE SHUTDOWN
Section [218]: 001-015 (000=disabled)
If in a 24-hour period, a trouble has occurred more
than the number of times programmed in section
[218], the control panel will no longer report this
trouble. Please note that each trouble its own
counter. This counter is reset every day at midnight
or when a Module Scan is performed (see section
12.7 of this manual). Also note that it can not be set
to more than 15.
12.17 NO AC FAIL DISPLAY
Section [503]: Option [7]
With option [7] in section [503] enabled, the control
panel will not display the AC Failure as a trouble.
This means that when an AC Failure occurs, the
AC LED will not illuminate, the trouble will not
appear in the Trouble Display and there will be no
trouble beep. The AC Failure report code, however,
will be reported.