EasyManuals Logo

Paradox MG5000+ User Manual

Paradox MG5000+
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
MG5000+ / MG5050+ Installation Guide
23
Zone Programming
When programming zones, the zone assignments are dependent on the designation of the wireless transmitters, assignment of keypad zones, and the detection
devices that are connected to the panel. For keypad assignment, see “Configuring the Keypad Zone Number” on page 16. After assigning the required zones, you
must set the zone’s definitions, partition assignment, and options see Figure 7 below. Certain Zone Definitions change if a Flex-Instant delay is activated (section
[720]). See see “Zone Definition Status” on page 26.
Table 1: Zone Recognition Table
NOTE: If a zone is already programmed and you assign a device to the same zone, a wireless zone will overwrite a keypad/hardwire zone, and a keypad zone will
overwrite a hardwire zone.
Figure 7: Zone Programming
Zone Definitions
As demonstrated in Figure 8 above, sections [001] to [032] represent zones 1 through 32 respectively, where the first two digits in each of these sections represents
the zone's definition. To disable a zone, enter [00]. There are 26 available Zone Definitions.
Entry Delay 1 Zones
Sections [001] to [032]: Zones 1 to 32, First Digits = 01
When the system is armed and a zone defined with Entry Delay 1 opens, the control panel will generate an alarm after the programmed Entry Delay 1 Timer elapses.
This is to provide users with enough time to enter the protected area and disarm the system. To program the Entry Delay 1 Timer, key in the desired 3-digit delay
value (000 to 255 seconds, Default = 45 seconds) into section [710]. Entry delay zones are commonly used at the entry/exit points of the protected area (e.g., front/
back door, garage, etc.). Using different entry delays is useful when, for example, one entry point requires a longer delay than the other entry point or in a
partitioned system where each partition may require a different entry delay.
Entry Delay 2 Zones
Sections [001] to [032]: Zones 1 to 32, First Digits = 02
Entry Delay 2 zones are identical to the Entry Delay 1 zones, except it uses a separate entry delay timer. To program the Entry Delay 2 Timer, key in the desired 3-digit
delay value (000 to 255 seconds, Default = 45 seconds) into section [711].
Entry Delay 1 (Full Arm) Zones
Sections [001] to [032]: Zones 1 to 32, First Digits = 03
Upon regular arming, the zone is Entry Delay 1 (see “Entry Delay 1 Zones” on page 23). Upon Stay/Sleep arming, the zone is bypassed by the system. See Zone
Definition Status on page 26 for any exceptions.
Wireless Keypad Hardwire
Zone 1 Yes Yes Yes (Input Z1)
Zone 2 Yes Yes Yes (Input Z2)
Zone 3 Yes Yes Yes (Input Z1 with ATZ)
Zone 4 Yes Yes Yes (Input Z2 with ATZ)
Zone 5 to 32 Yes Yes No
Section Zone Definition Partition Assignment Zone Options
[001] = Zone 1 _____/_____ _____________ 1 2 3 4 5 6 7 8
[032] = Zone 32 _____/_____ _____________ 1 2 3 4 5 6 7 8

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Paradox MG5000+ and is the answer not in the manual?

Paradox MG5000+ Specifications

General IconGeneral
StayD ModeYes
Zones32
Wireless ExpansionYes
Remote ControlYes
PGMs2
Remote ControlsCompatible with MG/SP remote controls
Battery Backup12V 7Ah battery (not included)
Outputs2 programmable outputs

Related product manuals