Programming D-141
DC590+ DRV Series DC Digital Drive
Operation Description
WINDOW
This function outputs TRUE when INPUT A is within a programmable range, and FALSE otherwise.
INPUT B sets the threshold of the window to be monitored. INPUT C defines the range of the window around the threshold.
When the value of INPUT A is inside the window, the window expands by 0.01 to avoid flutter on output if noisy, i.e. if
INPUT B = 5 and INPUT C = 4 then the range is 3 to 7, expanded to 2.5 to 7.5 when the value if INPUT A is inside the
window.
If INPUT C is set to zero, the output will only be TRUE if INPUT A is exactly equal to INPUT B (this is fulfilled in the
default condition when inputs A, B & C are all zero)
If INPUT C is set to a negative value, its absolute value defines the window range, and the output is inverted.
input A
output
input B threshold
input C window width
input C +ve
input C -ve