2.7 Conditions of utilization for CE-conform operation
- Industry and trade -
The EC guidelines for electromagnetic compatibility 2004/108/EC and for electrical
operating devices for utilization within certain voltage limits 2006/95/EC are fulfilled
when the following boundary conditions are observed:
Operation of the devices only in the condition in which they were delivered,
i.e. with all housing panels.
Shielding connection of the valve cables
The cable must be fully-screened and connected to the Compax3 housing. Use the
cable clamps/shield connecting terminals furnished with the device.
The shield of the valve cable must also be connected with the valve housing. The
fixing (via plug or screw in the terminal box) depends on the valve type.
< 100 m
Use only with aligned controller (to avoid control loop oscillation).
Signal lines and power lines should be installed as far apart as possible.
Signal lines should never pass close to excessive sources of interference
(motors, transformers, contactors etc.).
Do not place mains filter output cable parallel to the load cable.
Make sure to use only the accessories recommended by Parker
Connect all cable shields at both ends, ensuring large contact areas!
This is a product in the restricted sales distribution class according to EN
61000-6-4. In a domestic area this product can cause radio frequency
disturbance, in which case the user may be required to implement
appropriate remedial measures.
Compax3 encoder
cable:
Control:
Cable installation:
Accessories:
Warning: