Parker Hannifin S.p.A. - Divisione S.B.C. “SPD” User’s Manual
27
The following messages may be displayed on the screen, in addition to the value of the
parameters and the instructions of the pico-PLC:
r. xx When the converter is powered on, this message indicates which version of the software
is installed.
IdLE When the converter is powered on and corresponding to Pr0, this message
indicates that there is no alarm and that the converter is off.
run When the converter is powered on and corresponding to Pr0, this message indicates that
there is no alarm and that the converter is on. The motor shaft may be rotating.
Er. xx Corresponding to Pr0, this message indicates that the converter has registered an
alarm (xx indicates the alarm code) and has shut off. When it registers an alarm, the converter
is brought to Pr0, displaying the alarm code.
Pr. xx Indicates the parameter xx whose value can be displayed by pressing the [M] key.
Pb. xx Indicates the parameter at bit xx.
bxx.yy Indicates the bit yy of parameter xx. By pressing the [M] key, the status of the bit
is displayed.
In. xx Indicates instruction xx of the PLC program.
donE Is displayed for about 1 second whenever a command is sent.
rESet Is displayed for about 1 second whenever an alarm reset command is sent
(b99.10).
dEF Indicates that the drive is set to default status and must be programmed with the basic
parameters of the motor.
triP.x Indicates that the converter has malfunctioned.
IF YOU CANNOT MODIFY THE READ-WRITE PARAMETERS USING THE
KEYPAD, BE SURE THAT PB99.7 IS 0; IF IT WAS 0, PROBABLY THE SAME
PARAMETERS WERE MODIFIED BY THE PLC PROGRAM.