EasyManua.ls Logo

Parker SPD 2 - Serial Interface; Communication Protocol

Parker SPD 2
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parker Hannifin S.p.A. - Divisione S.B.C. “SPD” User’s Manual
78
13 SERIAL INTERFACE
The serial communication of the converter is half-duplex, master-slave, using an
asynchronous RS-485/RS-422 line. The converters take control of the line only if interrogated
by the master.
The same serial line can be connected to up to 32 converters by setting a different serial
address in each to the Pr27 parameter. It is also possible to set the transmission speed by using
the Pr26 parameter as specified in the table below:
(*) The version with code Pr26=4 differs from Pr26=5 for the delay of the response of 25 ms.
This version has been developed to interface with the PLCs that require such a feature.
For the connection diagrams, see the section, Connecting the serial line.
13.1 Communication protocol
The column on the right in the table above shows the time-out value expressed in
milliseconds for each communication speed. This is the time within which the message must
be sent, beginning from the start of each message (STX). If a message is interrupted after this
time, the converter ignores what has been received and waits for the beginning of a new
message. The message consists of several consecutive bits. The format of the bits is the
following:
1 start bit
8 bit of data defined by a following byte enclosed within brackets
1 parity bit (even)
1 stop bit
The structure of the message is the following:
[STX] [CMD+ADDR] [BK+LUN] [PAR] [D0]... [Dn] [CHK]
where:
[STX] = $7E indicator of transmission start. If a field in the message different from STX
assumes the value $7E, this field is followed by a 0 ($00) so that it will not be interpreted as
an [STX].
[CMD+ADDRESS] = command and address of the device. This data is composed in the
following way: the first 5 bits (bits 0-4) define the address of the converter (from 0 to 31);
the remaining 3 bits (bits 5-7) define the type of message sent, as described in the following
table:
Pr26 (decimal base) b/s time-out (ms)
0 600 512
1 1200 256
2 2400 128
3 4800 64
4 9600 (*) 32
5 9600 32
6 19200 16
7 38400 12
8 57600 8

Table of Contents

Related product manuals