MIC 1161 Manual
30
8 Com Address CAd 1 - 32 1
9 CJC Enable CJC EnAb EnAb
diSA
* The Hardware Definition Code and input jumper configuration may need
to be changed. See Appendix B and C.
TABLE 3-3 SET-UP MODE
To enter the Set-Up mode, press and release the SCROLL key until "SEt"
is displayed. Use the DOWN key to enter the Set-Up mode. The "S" LED
should be lit. Depress and release the SCROLL key to sequence through
the parameters and their values, alternately showing the parameter code in
the lower display with the upper display blank, then the parameter code
with the parameter value displayed. Use the UP and DOWN keys to adjust
the parameter values. After adjusting a parameter, depress the SCROLL
key to proceed to the next parameter. Use the DOWN key to advance to
the next parameter when a parameter code is showing in the lower display
and the upper display is blank.
To exit the Set-Up mode, press the UP key whenever a parameter code is
displayed in the lower display and the upper display is blank.
1 Limit Setpoint SP ± Span 150**
2 Maximum Hold HiHd Read Only
3 Minimum Hold LoHd Read Only
4 Time Exceeded tLE Read Only
5 Input Filter Filt 0.0 to 100.0 2.0
seconds in .5
second increments
6 Hysteresis HySt 0 to 10% of span, 1
Limit Output expressed in units
DISPLAY AVAILABLE FACTORY
STEP DESCRIPTION CODE SETTINGS SETTING