EasyManua.ls Logo

Partlow MIC 1161 - Specifications (Appendix E); Input Specifications

Partlow MIC 1161
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
43 MIC 1161 Manual
Appendix E
Specifications
INPUT SPECIFICATIONS
General
Input Sample Rate: Four per second
Input Resolution: 14 bits approximately
Input Impedance: Greater than 100M ohm resistive
(except for DC mA and V inputs)
Isolation: Universal input isolated from all outputs
except SSR at 240 VAC.
Thermocouple
Types: R, S, J, T, K, L, B and N
Sensor Break Protection: Break detected within 2 seconds. Limit
Relay OFF, alarms operate as if the process
variable has gone over-range.
RTD and DC mV
Type and Connection: Three-wire Pt100 (.00385 ohm/ohm/C)
Lead Compensation: Automatic
Sensor Break Protection: Break detected within 2 seconds. Limit
Relay OFF, alarms operate as if the process
variable has gone under-range.
DC mA and DC V
Scale Range Maximum: -1999 to 9999
Scale Range Minimum: -1999 to 9999
Minimum Span: 1 display LSD
Sensor Break Protection: Applicable to 4-20mA, 1-5V, and 2-10V
ranges only. Break detected within 2
seconds. Limit Relay OFF, alarms operate as
if the process variable has gone under-range.
Remote Reset
Type: Voltage free contact, closure required to reset.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com