Installer manual Fleck 2850 SXT - Programming
56 / 104 Ref. MKT-IM-030 / C - 12.05.2020
6.5.6 Number of tanks (NT)
Select the number of tanks.
Options:
• NT1: single tank system;
• NT2: double tanks system.
Mandatory
Due to the 2850 valve being designed for single tank system only, set valve type to1.
1. Press or until "---1" is displayed.
2. Press to validate the selection and move to the next parameter.
6.5.7 Tank in service (TS)
Info
This parameter appears only if number of tanks(NT) is set to2.
If it appears, the 2850 valve being a single tank system, go back to number of tanks (NT)
and set it to1.
6.5.8 Unit capacity (C)
Set the unit capacity.
Mandatory
Enter the capacity of the media bed in m
3
x °TH or g as CaCO
3
for softener system (Cis
displayed in the upper left corner) or in litres for filter (Vis displayed in the upper left
corner)!
Info
The unit capacity parameter is only available if the controller type has been
programmed for volumetric regeneration.
The unit capacity can be set from0.1 to9999 x 1000°TH*m
3
, g as CaCO
3
equivalent or in
grains if DF=GAL.
1. Press or to select the unit capacity.
2. Press to validate the selection and to move the next parameter.