EasyManuals Logo

Pepperl+Fuchs VisuNet RM Shell 6 User Manual

Pepperl+Fuchs VisuNet RM Shell 6
171 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #165 background imageLoading...
Page #165 background image
VisuNet RM Shell 6
Appendix
2023-05
165
12 Appendix
12.1 Open Network Ports
For communication between Control Center and RM Shell, the TCP port 8023 is used.
For the detection of existing RMs / BTCs (scan) use the UDP/TCP port 3702.
There is no DNS server for the NetBIOS translation. UDP port 137 is required.
Port TCP UDP Description
3702 and 137 - UDP VisuNet CC Discovery
8023 TCP - VisuNet CC Download/Upload
5900 TCP - VisuNet CC Session Shadowing
22314 TCP - VisuNet CC Default Secure Tunnel Port
23314 TCP - Factory Reset Communication Port