PLC / Modbus/RTU
105542_en_05 PHOENIX CONTACT 83 / 198
6.7 Error codes and formats for analog input and
output values
The measured value is represented in bits 0 ... 15. Values greater than 8000
hex
indicate an
error.
RAD-AI4-IFS analog inputs
RAD-AO4-IFS analog outputs
RAD-DAIO6-IFS analog inputs and outputs
Table 6-18 Representation of RAD-AI4-IFS analog values
Data word
hex dec/error code 0mA...20mA 4 mA ... 20 mA
0000 0 0 mA -
1770 6000 4 mA 4 mA
7530 30000 20 mA 20 mA
7F00 32512 21.67 mA 21.67 mA
8001 Overrange >21.67 mA >21.67 mA
8002 Open circuit - <3.2 mA
8080 Underrange <0 mA -
Table 6-19 Representation of RAD-AO4-IFS analog values
Data word
hex dec/error code 0mA...20mA 0 V ... 10 V
0000 0 0 mA 0 V
7530 30000 20 mA 10 V
7F00 32512 21.67 mA 10.84 V
Table 6-20 Representation of RAD-DAIO6-IFS analog values
Data word
hex dec/error code 0...20mA 4...20mA 0V...10V
0000 0 0 mA - 0 V
1770 6000 4 mA 4 mA 2 V
7530 30000 20 mA 20 mA 10 V
7F00 32512 21.67 mA 21.67 mA 10.84 V
8001 Overrange >21.67 mA >21.67 mA -
8002 Open circuit - <3.2 mA -
8080 Underrange <0 mA - -