PNOZ s5
Operating Manual PNOZ s5
21397-EN-10
30
Relay outputs 750135 751135
Utilisation category
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at 230 V 230 V
Max. current 3 A 3 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 4 A 4 A
Utilisation category of safety con-
tacts delayed
AC15 at 230 V 230 V
Max. current 3 A 3 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 4 A 4 A
Utilisation category in accordance
with UL
Voltage 240 V AC G.U. (same polarity) 240 V AC G.U. (same polarity)
With current 6 A 6 A
Voltage 24 V DC G. U. 24 V DC G. U.
With current 6 A 6 A
Pilot Duty B300, R300 B300, R300
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 66 A²s 66 A²s
Blow-out fuse, quick 6 A 6 A
Blow-out fuse, slow 4 A 4 A
Blow-out fuse, gG 6 A 6 A
Circuit breaker 24V AC/DC,
characteristic B/C 4 A 4 A
External contact fuse protection,
delayed safety contacts
Max. melting integral 66 A²s 66 A²s
Blow-out fuse, quick 6 A 6 A
Blow-out fuse, slow 4 A 4 A
Blow-out fuse, gG 6 A 6 A
Circuit breaker 24 V AC/DC,
characteristic B/C 4 A 4 A
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au