3-3Operating Manual: PSS SB 3006-3 Series
Digital inputs (DI2)
Depending on the application area and its respective regulations, the PSS
may be used without test pulses for applications up to category 3
in accordance with EN 954-1 (03/97). The possibility of a short circuit
occurring in the external wiring between different inputs or to L+ must be
eliminated through appropriate wiring.
Test pulses must be used for category 4 applications (for connection
examples please see Chapter 7, “Wiring the Inputs and Test Pulse
Outputs”).
Safety guidelines
Failure to keep to these guidelines will render all warranty and liability
claims invalid:
All health and safety / accident prevention regulations for the particular
area of application must be observed.
Before using the unit it is necessary to perform a safety assessment in
accordance with the Machinery Directive 98/37/EC.
Use of qualified personnel
The safety system may only be assembled, installed, programmed,
commissioned, operated, maintained and decomissioned by qualified
personnel. Qualified personnel are people who, because they are:
Qualified electrical engineers and
• Have received training from qualified electrical engineers,
are suitably experienced to operate devices, systems, plant and machinery
in accordance with the general standards and guidelines for safety
technology.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Other manuals for Pilz PSS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pilz PSS Series and is the answer not in the manual?

Pilz PSS Series Specifications

General IconGeneral
CategorySafety Equipment
ManufacturerPilz
Safety StandardsEN ISO 13849-1, IEC 61508, IEC 62061
SeriesPSS
Safety Integrity LevelSIL 3
Communication InterfacesEthernet, PROFIBUS, PROFINET
Operating Voltage24 V DC
Operating Temperature0°C to +55°C (typical), others depending on model
Storage Temperature-20°C to +70°C (typical), others depending on model
Protection ClassIP20
ApplicationIndustrial safety applications