36 ATR401 - User manual
13 Lower Linear Input 2
AI2 lower range limit only for linear signals. Example: with input 4...20 mA
this parameter takes value associated to 4 mA.
-999…+9999 digit
4
, Default: 0.
14 Upper Linear Input 2
AI2 upper range limit only for linear signals. Example: with input 4...20 mA
this parameter takes value associated to 20 mA
-999…+9999 digit
4
, Default: 1000.
15 O set Calibration 2
AI2 o set calibration. Number added to visualized process value (normally
correcting ambient temperature value).
-999…+1000 digit
4
for linear sensors and potentiometers.
-99.9…+100.0 tenths for temperature sensors, Default: 0.0.
16 Gain Calibration 2
AI2 Gain calibration. % Value multiplied with displayed value to calibrate
process value.
-99.9%…+100.0%, Default: 0.0.
17 Lower Limit Setpoint 2
AI2 lower limit setpoint.
-999…+9999 digit
4
(degrees i f temperature), Default: 0.
18 Upper Limit Setpoint 2
AI2 upper limit setpoint.
-999…+9999 digit
4
(degrees i f temperature), Default: 1750.
19 Command Process
Selects process value related to command output and visualized on
display 1. This determinates which is the primary process
Process 1 (Default)
Process 2
Process mean
Processes di erence
Processes di erence as absolute value
AI1+AI2 Input addition
4
The display of the decimal point depends on the setting of parameter
. and
or
and