ATR401 - User manual 49
 Enabled
 Enabled with memory
84  Digital Input
 Disabled (Default: 0)
 2 Setpoints Switch
 2 Setpoints Switch Impulsive
 3 Setpoints Switch Impulsive
 4 Setpoints Switch Impulsive
 Start / Stop
 Run N.O. (enables regulation with N.O. contact)
 Run N.C. (enables regulation with N.C. contact)
 Lock conversion N.O. (stop conversion and display value with
N.O.)
 Lock conversion N.C. (stop conversion and display value with
N.C.)
 Manual Tune (by digital input)
Automatic / Manual Impulse (if enabled on parameter 83)
Automatic / Manual Contact (if enabled on parameter 83)
 Action Type. Heating regulation with open D.I.
Cooling regulation with closed D.I
 Remote Setpoint enabling. Enables Remote setpoint with closed
D.I. Desables Remote setpoint with open D.I. (selection  must
be enabled on parameter 20  )
85  Rising Gradient
Rising gradient for Soft-Start
0 Disabled.
19999 Digit/hour
14
(degrees/hour with decimal visualization if
temperature), Default: 0.
86  Visualization Display 2
Set visualization on display 2
 Output Percentage
 Ampere
 Command Setpoint (Default)
 Process 1
 Process 2
 Processes mean