ATR 621 - User manual 43
73  Cooling Fluid
De nes cooling  uid type.
 > Default


74  Proportional Band Multiplier
1.005.00. > Default: 1.00.
75  Overlap/Dead Band
-20.0%…50.0%. > Default: 0.0%.
76  Cooling Cycle Time
1…300 seconds. > Default: 10s.
77  Remote Setpoint
Selects remote setpoint mode, through serial communication.
 (Disabled). Controller operates autonomously. > Default.
 (Slave). Controller is a slave normally in STOP: goes in RUN when,
on master device connected to the serial, a cycle is started.
 (Master). Controller transmits the setpoint to all controllers
connected to the serial and set as slave.
78 bd.rt. Baud Rate
Selects baud rate for serial communication.
 4800 bit/s
 9600 bit/s  38400 bit/s
 19200 bit/s > Default  57600 bit/s
 28800 bit/s  115200 bit/s
79  Serial Parameters Setting
Selects data format for serial communication.
  8 data bits, no parity, 1 stop bit. > Default.
  8 data bits, odd parity, 1 stop bit.
  8 data bits, even parity, 1 stop bit.
80  Slave Address
Selects slave address for serial communication.
1…254 Address for slave functioning. > Default: 254.