77
2
Type T (-250/400°C)
3
Type R (-50/1750°C)
4
Type J (-200/1000°C)
5
Type E (-250/1000°C)
3
rd
Digit - Decimal point
0
No decimal point
1
Visualization with one decimal point
2
Visualization with 2 decimal points (only V /mA)
3
Visualization with 3 decimal points (only V /mA)
4
th
Digit Select process
0
Process 1
(* ex. Pressure or humidity sensor connected to analog input
AN2 is Process 1)
1
Process 2
P-04
Reserved
P-05
Configuration control outputs and source of setpoints
(ex.: TC1 on AN1 configured as process 1 on Out and
TC2 on
AN2 as process 2 on A1) and select source of setpoint (** Only
Setpoint1 changes according to the programmed cycle, while
Setpoint2 can only be fixed.
1
st
Digit Control output process 1
2
nd
Digit Control output process 2
0
No output or isabled process
1
Relay OUT contact N.O.
2
Relay OUT contact N.C.
3
Relay A1 contact N.O.
4
Relay A1 contact N.C.
5
Relay or SSR A2 contact N.O.
6
Relay or SSR A2 contact N.C.
7
Open/Close contact N.O. (Open OUT, Close A1)
8
Open/Close contact N.C. (Open OUT, Close A1)
3
rd
DigitSource of setpoint for process 1 + process 2
Process 1 Process 2
0
Setpoint1 (cycle data) Setpoint1 (cycle data)
1
Setpoint1 (cycle data) Setpoint2 (fixed)
2
Setpoint2 (fixed) Setpoint1 (cycle data)