81
0
Only process1
1
Only process 2
2
Add process 1 and process 2
3
rd
Digit Real time/duration of cycle
26
0
No
1
yes
4
th
Digit Visualization of step
0
Step number always visualized in programming mode
1
Step number visualized only at beginning of step
(equivalent to the operating in programming mode of series
ATR610)
P-20
Power of heating elements (0.0/999.9 Kwatt).
Enter power of heating elements group. If the programmed value
is different from 0, it will be possible to visualize power
consumption (expressed as Kwatt/hour) at cycle end pressing
key
P-21
Waiting for step end (1/1440 min, 0 excludes waiting function)
Enter max. waiting time for step end. For further details see 31.3
P-22
Max. gap at step end to activate waiting function
(1/200 digit).
When the gap setpoint-process 1 is lower than this value, the
controller jumps to next step of cycle without waiting for the time
entered on P-21. For further details see 31.3
P-23
Recovery of interrupted cycle
This parameter enables recovery of interrupted cycle after a
power failure. For further details see 31.1-31.2
0
Cycle recovery isabled
1
Cycle recovery enabled (see 31.1)
2-9999
Recovery gradient (rising) as degree/hour (see 31.2)
P-24
Reserved
26
Pressing , during cycle, the visualized time value will be the time
elapsed after cycle start, not the programmed time. PPressing after cycle
Stop to visualize duration of last cycle.