Electrical Specifications
DA500 Chillers
Max. Operating
Current / Fuse –
Circuit Breaker Size
with no heaters
Max. Operating
Current / Fuse –
Circuit Breaker Size
with 3000 Watt Heater
Option
Max. Operating
Current / Fuse –
Circuit Breaker Size
with 7500 Watt Heater
Option
Max. Operating
Current / Fuse –
Circuit Breaker Size
with 9000 Watt Heater
Option
Model
Voltage / Phase /
Hertz
Max.
Amps
Fuse –
CB Size
Max.
Amps
Fuse –
CB Size
Max.
Amps
Fuse –
CB Size
Max.
Amps
Fuse –
CB Size
DA504F 208-230V / 3 / 50-60 29.4 45 36.6 55 47.4 70 51.1 75
DA504G 208-230V / 3 / 50-60 32.6 50 39.8 60 50.6 75 54.3 80
DA504C3 208-230V / 3 / 50-60 35.1 55 42.3 65 53.1 80 56.8 80
DA504C5 208-230V / 3 / 50-60 39.7 60 46.9 75 57.7 85 61.4 85
DA504D1/S1 208-230V / 3 / 50-60 31.4 50 38.6 60 49.4 75 53.1 80
DA504D2/S2 208-230V / 3 / 50-60 35 55 42.2 65 53 80 56.7 80
DA504D3/S3 208-230V / 3 / 50-60 39 60 46.2 70 57 85 60.7 85
DA504D6/S6 208-230V / 3 / 50-60 32.6 50 39.8 60 50.6 75 54.3 80
DA506F 380V / 3 / 50 15.2 25 18.8 30 26 40
DA506G 380V / 3 / 50 16.7 25 20.3 30 27.5 40
DA506C3 380V / 3 / 50 17.2 25 20.8 30 28 40
DA506C5 380V / 3 / 50 18.3 30 21.9 35 29.1 45
DA506D1/S1 380V / 3 / 50 16.2 25 19.8 30 27 40
DA506D2/S2 380V / 3 / 50 18.1 30 21.7 35 28.9 45
DA506D3/S3 380V / 3 / 50 19.6 30 23.2 35 30.4 45
DA506D6/S6 380V / 3 / 50 16.8 25 20.4 30 27.6 40
DA508F 460V / 3/ 60 15.4 25 19 30 26.2 40
DA508G 460V / 3/ 60 16.9 25 20.5 30 27.7 40
DA508C3 460V / 3/ 60 18 30 21.6 35 28.8 45
DA508C5 460V / 3/ 60 20 30 23.6 35 30.8 45
DA508D1/S1 460V / 3/ 60 16.2 25 19.8 30 27 40
DA508D2/S2 460V / 3/ 60 17.5 25 21.1 35 28.3 40
DA508D3/S3 460V / 3/ 60 20.2 30 23.8 35 31 45
DA508D6/S6 460V / 3/ 60 16.4 25 20 30
NA
27.2 40
For 575 Volt units consult the factory
110-279 39