DW500 Chillers
Max. Operating
Current / Fuse –
Circuit Breaker Size
with no heaters
Max. Operating
Current / Fuse –
Circuit Breaker Size
with 3000 Watt Heater
Option
Max. Operating
Current / Fuse –
Circuit Breaker Size
with 7500 Watt Heater
Option
Max. Operating
Current / Fuse –
Circuit Breaker Size
with 9000 Watt Heater
Option
Model
Voltage / Phase /
Hertz
Max.
Amps
Fuse –
CB Size
Max.
Amps
Fuse –
CB Size
Max.
Amps
Fuse –
CB Size
Max.
Amps
Fuse –
CB Size
DW504F 208-230V / 3 / 50-60 25.4 40 32.6 50 43.4 70 47.1 70
DW504G 208-230V / 3 / 50-60 28.6 45 35.8 55 46.6 70 50.3 75
DW504C3 208-230V / 3 / 50-60 31.1 50 38.3 60 49.1 75 52.8 80
DW504C5 208-230V / 3 / 50-60 35.7 55 42.9 65 53.7 80 57.4 80
DW504D1/S1 208-230V / 3 / 50-60 27.4 45 34.6 55 45.4 70 49.1 75
DW504D2/S2 208-230V / 3 / 50-60 31 50 38.2 60 49 75 52.7 80
DW504D3/S3 208-230V / 3 / 50-60 35 55 42.2 65 53 80 56.7 80
DW504D6/S6 208-230V / 3 / 50-60 28.6 45 35.8 55 46.6 70 50.3 75
DW506F 380V / 3 / 50 13.2 20 16.8 25 24 35
DW506G 380V / 3 / 50 14.7 25 18.3 30 25.5 40
DW506C3 380V / 3 / 50 15.2 25 18.8 30 26 40
DW506C5 380V / 3 / 50 16.3 25 19.9 30 27.1 40
DW506D1/S1 380V / 3 / 50 14.2 20 17.8 30 25 40
DW506D2/S2 380V / 3 / 50 16.1 25 19.7 30 26.9 40
DW506D3/S3 380V / 3 / 50 17.6 25 21.2 35 28.4 40
DW506D6/S6 380V / 3 / 50 14.8 25 18.4 30 25.6 40
DW508F 460V / 3/ 60 13.3 20 16.9 25 24.1 35
DW508G 460V / 3/ 60 14.8 25 18.4 30 25.6 40
DW508C3 460V / 3/ 60 15.9 25 19.5 30 26.7 40
DW508C5 460V / 3/ 60 17.9 30 21.5 35 28.7 40
DW508D1/S1 460V / 3/ 60 14.1 20 17.7 30 24.9 40
DW508D2/S2 460V / 3/ 60 15.4 25 19 30 26.2 40
DW508D3/S3 460V / 3/ 60 18.1 30 21.7 35 28.9 40
DW508D6/S6 460V / 3/ 60 14.3 20 17.9 30
NA
25.1 40
For 575 Volt units consult the factory
110-279 40