6.5.2. 18 Pulses Configuration Example
General characteristics:
Secondary winding phase shift (º): +20º, 0º, -20º
Nominal secondary windings voltage (V): 3xVn
1
Recommended Tap voltage on primary side (%): ±10%
Total Nominal current (A): In (A)
Total Overload (A): 120% ND (60 seconds)
150% HD (60 seconds)
Short circuit Impedance (%): < 7%
Secondary winding power factor: 0.90
Recommended Rated Power (kVA): +20% Motor Power
SD700 18 pulses connection scheme:
Figure 6.13 SD700 18 pulses
1
For improved performance, it is recommended to increase a 3% the nominal secondary voltage.