FAULT MESSAGES. DESCRIPTIONS AND ACTIONS
Motor stalled. Heavy load.
Motor mechanical brake is coupled.
Check the motor load.
Increase maximum current limit.
Motor stalled. Heavy load.
Motor mechanical brake is coupled.
Check the motor load.
Increase maximum torque limit.
Speed reference is lower or equal than the speed
limit.
Check the reference source and the motor load.
Motor speed is out of control or motor is not
accelerating due to the load.
High current used by the motor due to heavy
load.
Check the motor load.
Check the setting of parameters „G2.1 MTR CUR‟
and „G2.7 MTR COOL‟ relating to the motor
thermal model. Increasing the parameter „G2.7
MTR COOL‟, can be undertaken when there is a
motor PTC fitted and it is connected to the
SD700FR.
The load exceeds the capacity of motor cooling
under normal operating conditions.
Incorrect setting of the thermal model
parameters.
Phase loss of the motor or a fault in motor
windings.
Excessive regeneration is produced due to
deceleration ramp to high.
Decrease deceleration ramp.
Revise the setting of parameters related to
regenerating current limitation (G10.12 and
G10.13).
Disconnect and connect again SD700FR input
power. If the same fault appears, initialize all of
the parameters (parameter „G1.5 INITIALISE‟)
and connect the input power again. If the fault
persists, request technical assistance.
Parameter setting is incoherent.
Reset the fault; If the fault persists, request
technical assistance.
Blocked or poor ventilation.
Check if there is an object blocking ventilation.
Improve the cooling.
Heat sink and cooling fan fault on the SD700FR.
Check if the heat sink and the cooling fan are
operating correctly.
Ambient temperature is higher than 50°C.
Check the cooling and thermal conditions.
Request technical assistance.
The DSP software version of the inverter and the
rectifier bridges are different.
Check these two software versions with the
display.
Check CAN communications.
External trip device has operated.
Check the external trip switch (if exists).
Motor is overheated (motor load exceeds the
cooling capacity at operating speed).
Check motor temperature.
To reset the fault the motor must be return to
normal temperature.
Fault in sensor connection.
Trip generated by a computer through serial
communication.
Disconnect the SD700FR from the
communication network and verify if the fault is
generated again.
Analogue input cable has been come loose or
disconnected (terminals 10 and 11).
Verify the wiring and the device which provides
the analogue signal.
Analogue input cable has been come loose or
disconnected (T12 and T13).
Verify the wiring and the device which provides
the analogue signal.
Verify drive select. Request technical assistance.
Deceleration ramps (parameters „G5.2 DECEL1‟
and „G5.4 DECEL2‟) are too slow.
Verify that the time set in parameter „G11.2 STOP
TO‟ to stop the system after setting deceleration
ramps and checking the system performance.
SD700FR is voltage limiting voltage due to
regeneration from the motor.
Integrated circuit fault.
Request technical assistance.
Communications cable has been come loose or
cut.
Verify the wiring of communications system.
Master device has not sent valid data in the
required frame or it has sent incorrect data.
Verify the data and settings of the master device.