Stand alone drives
Frames 5 to 11 are designed to be placed over a technical floor. If necessary, there are optional plinths
that increase the height of the drive from 1710 mm to 2000 mm or 2200 mm. The floor must guarantee
a non-flammable, solid, plain and level surface to the drive, a minimum safety distance around it and
esay cable access. The maximum allowed slope is 1cm per 6 meters. The installation site should be
level since the cabinet is not equipped with a height-adjustable base. The walls adjoining the drive
must be of a non-flammable material. Attach the SD750 to the wall or floor using the L brackets on both
sides of the drive. The brackets have Ø11 hole diameters and are located on the legs and rear.
Wall or floor fixation
It is recommended to construct a cable duct to get the cables to the input / output connections. The
duct width must not exceed 300 mm and the ground contact surface must withstand the weight of the
cabinet that falls on its legs.