Appendix I
128
Auxiliary frequency display
Note:
There are two ways to modify the settings frequencies through communication mode:
The first: Set F0.03 (Main frequency source setting) as 0/1 (keyboard set frequency), and then
modify the settings frequency by modifying F0.01 (keyboard set frequency). Communication
mapping address of F0.01 is 0xF001 (Only need to change the RAM communication mapping
address to 0x0001).
The second:Set F0.03 (Main frequency source setting) as 9 (Remote communication set), and
then modify the settings frequency by modifying (Communication settings). , mailing address of
this parameter is 0x1000.The communication set value is the percentage of the relative value,
10000 corresponds to 100.00%, -10000 corresponds to -100.00%. For frequency dimension data, it
is the percentage of the maximum frequency (F0.19); for torque dimension data, the percentage is
F5.08 (torque upper limit digital setting).
Control command is input to the inverter: (write only)
0006: Deceleration and stop
Inverter read status: (Read-only)
Parameter lock password verification: (If the return code is8888H, it indicates that password
verification is passed)
Digital output terminal control: (write only)
BIT0: SPA output control
BIT1: RELAY2 output control
BIT2 RELAY1 output control
BIT3: Manufacturer reserves the undefined
BIT4: Reserve