SECTION 5 - TECHNICAL DATA
QUANTECH
63
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
5
TABLE 6 - PHYSICAL DATA - ROUND TUBE COIL (CONT'D)
UNIT FRAME 320 330 340 370 405 450 460 470 480 500
CONDENSER CODE S S S S S S S C C S
EVAPORATOR CODE E C E F H G G K J J
GENERAL UNIT DATA
Number of Independent
Refrigerant Circuits
2
Refrigerant Charge, R-134a,
R-513A, Ckt.-1/Ckt.-2, lbs (kg)
367/367
(166/166)
371/371
(168/168)
391/391
(177/177)
537/308
(244/140)
568/417
(258/189)
478/478
(217/217)
502/502
(228/228)
480/480
(218/218)
495/495
(224/224)
562/562
(255/255)
Oil Charge, Ckt.-1/Ckt.-2,
gal (liters)
3.7/3.7
(14.0/
14.0)
3.7/3.7
(14.0/
14.0)
3.8/3.8
(14.4/
14.4)
4.0/2.9
(15.1/
11.0)
4.0/4.0
(15.1/
15.1)
4.0/4.0
(15.1/
15.1)
4.0/4.0
(15.1/
15.1)
4.0/4.0
(15.1/
15.1)
4.0/4.0
(15.1/
15.1)
4.2/4.2
(15.9/
15.9)
Minimum Load (%) 10%
Chassis Dimensions - Length,
inches (mm)
379.2
(9631)
423.1
(10748)
423.1
(10748)
467.1
(11864)
467.1
(11864)
555.3
(14104)
599.3
(15222)
467.1
(11864)
467.1
(11864)
599.3
(15222)
Chassis Dimensions - Width,
inches (mm)
88.3
(2242)
88.3
(2242)
88.3
(2242)
88.3
(2243)
88.3
(2243)
88.3
(2243)
88.4
(2244)
88.3
(2242)
88.4
(2244)
88.3
(2243)
Chassis Dimensions - Height,
inches (mm)
94.6
(2403)
94.6
(2403)
94.6
(2403)
94.7
(2405)
94.7
(2405)
94.7
(2405)
94.7
(2405)
94.6
(2403)
94.7
(2405)
94.7
(2405)
COMPRESSORS, SEMI-HERMETIC SCREW
Qty per Chiller 2
CONDENSER FANS
Number Ckt-1/Ckt-2 8/8 9/9 9/9 13/7 12/8 12/12 13/13 10/10 10/10 13/13
Air on Condenser
(Min/Max), °F (°C)
0/125
(-17.8/51.7)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM
Water Volume, gal (liters) 113 (428) 71 (269) 113 (428) 96 (363) 130 (492) 96 (363) 96 (363) 130 (492) 147 (556) 147 (556)
Leaving Water Temperature
(Min/Max), °F (°C)
2
40/60
(4.4/15.6)
Maximum Water Side
Pressure, psig (barg)
150
(10.3)
Maximum Refrigerant Side
Pressure, psig (barg)
235
(16.2)
Evap Drain Connection,
inches (mm)
3/4
Minimum Chilled Water Flow
Rate, gpm (l/sec)
400
(25.2)
300
(18.9)
400
(25.2)
460
(29.0)
520
(33.0)
460
(29.0)
460
(29.0)
470
(30)
550
(34.1)
550
(34.1)
Maximum Chilled Water Flow
Rate, gpm (l/sec)
1500
(94.7)
1150
(72.6)
1500
(94.7)
1540
(97.0)
1700
(107.0)
1540
(97.0)
1540
(97.0)
1870
(118)
1880
(118.1)
1880
(118.1)
Inlet and Outlet Water
Connections, in
8 6 8 8 8 8 8 8 8 8
NOTES:
1. Shipping and operating weights shown are for base unit; selected options may add weight to unit. Contact your nearest Quantech Sales
Representative for weight data.
2. For leaving liquid temperature below 40°F(4.4°C) or above 60°F (15.6°C). Contact your nearest Quantech Sales Representative for applica-
tion requirements.