SECTION 2 – PRODUCT DESCRIPTION
FORM QWC3-NM1
ISSUE DATE:11/20/2020
QUANTECH
15
2
Programmable setpoints
Chilled liquid temperature setpoint and range
Remote reset temperature range
Set daily schedule/holiday for start/stop
Manual override for servicing
LOW liquid temperature cutout
LOW suction pressure cutout
High discharge pressure cutout
Anti-recycle timer (compressor start cycle time)
Anti-coincident timer (delay compressor starts)
Displayed Data
Return and leaving liquid temperature
Low leaving liquid temperature cutout setting
Metric or Imperial data
Discharge and suction pressure cutout settings
System discharge and suction pressure
Anti-recycle timer status for each compressor
Anti-coincident system start timer condition
Compressor run status
No cooling load condition
Day, date and time
Daily start/stop times
Holiday status
Automatic or manual system lead/lag control
Lead system denition
Compressor starts and operating hours (each com-
pressor)
Run permissive status
Number of compressors running
Liquid solenoid valve status
Load and unload timer status
Water pump status
System Safeties
Cause individual compressors to perform auto shut
down and require manual reset in the event of three
trips in a 90-minute time period:
High discharge pressure
Low suction pressure
High pressure switches
Motor protector
Unit Safeties
Unit Safeties are automatic reset and cause all com-
pressors to shut down:
Low leaving chilled liquid temperature
Under voltage
Loss of liquid ow (through ow switch)
Low battery
Power and Control Panels
All power and controls are contained in an IP32 cabi-
net with hinged, latched and gasket sealed outer doors.
POWER PANEL
The power panel includes:
A factory mounted Non-fused Disconnect Switch
with external, lockable handle to enable connec-
tion of the unit power supply. The disconnect
switch can be used to isolate the power for servic-
ing.
Factory mounted compressor contactors and man-
ual motor starters to provide overload and short
circuit protection.
Factory mounted control transformer to convert
the unit supply voltage to 115V, 1-phase, 60Hz for
the control system.