SECTION 5 – TECHNICAL DATA
QUANTECH
42
Voltage Limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
Excessive ow will cause damage to the
cooler. Do not exceed max. cooler ow.
Special care should be taken when mul-
tiple chillers are fed by a single pump.
TABLE 4 - VOLTAGE LIMITATIONS
UNIT POWER MIN. MAX.
200-3-60 180 220
208-3-60 187 229
230-3-60 200 254
380-3-60 342 402
460-3-60 414 508
575-3-60 520 635