SECTION 9 – SERVICE AND TROUBLESHOOTING
FORM QWC3-NM1
ISSUE DATE:11/20/2020
QUANTECH
165
9
PROBLEM CAUSE SOLUTION
LACK OF COOLING EFFECT
1. Fouled evaporator surface Low
suction pressure will be observed.
1. Contact the local Quantech Sales
Representative.
2. Improper ow through the
evaporator.
2. Reduce ow to within chiller design
specs. See Limitations in SECTION
4 - INSTALLATION.
3. Low refrigerant charge. Low
suction pressure will be observed.
3. Check subcooling and add charge
as needed.
TABLE 26 - TROUBLESHOOTING (CONT’D)