SECTION 10 – MAINTENANCE
QUANTECH
180
TABLE 30 - YORKTALK 2 COMMUNICATIONS DATA MAP (CONT’D)
Address Scale Imperial SI
Point List Description 12345678910
P48 BV117 YT2_ S02_ P48 nvoYTS02p048 SNVT_switch (95)
BD 46 0177 N/A
0/1 0/1 YCWL Mode [0=Chiller, 1=Heatpump] NOOO
P49 BV118 YT2_ S02_ P49 nvoYTS02p049 SNVT_switch (95)
BD 47 0178
NNNN
P50 BV119 YT2_ S02_ P50 nvoYTS02p050 SNVT_switch (95)
BD 48 0179 N/A
0/1 0/1 SCC Auto Detect Digit 1 NSSS
P51 BV120 YT2_ S02_ P51 nvoYTS02p051 SNVT_switch (95)
BD 49 0180 N/A
0/1 0/1 SCC Auto Detect Digit 2 NSSS
P52 BV121 YT2_ S02_ P52 nvoYTS02p052 SNVT_switch (95)
BD 50 0181 N/A
0/1 0/1 SCC Auto Detect Digit 3 NSSS
P53 BV122 YT2_ S02_ P53 nvoYTS02p053 SNVT_switch (95)
BD 51 0182 N/A
0/1 0/1 SCC Auto Detect Digit 4 NSSS
P54 BV123 YT2_ S02_ P54 nvoYTS02p054 SNVT_switch (95)
BD 52 0183 N/A
0/1 0/1 SCC Auto Detect Digit 5 NSSS
P55 BV124 YT2_ S02_ P55 nvoYTS02p055 SNVT_switch (95)
BD 53 0184 N/A
0/1 0/1 SCC Auto Detect Digit 6 NSSS
P56 MV101 YT2_ S02_ P56 nvoYTS02p056 SNVT_count_f (51) ADI 25 0130
x1
None None Refrigerant [0=R-22, 1=R-407c, 2=R-410a] N S S S
P57 MV102 YT2_ S02_ P57 nvoYTS02p057 SNVT_count_f (51) ADI 26 0131
NNNN
P58 MV103 YT2_ S02_ P58 nvoYTS02p058 SNVT_count_f (51) ADI 27 0132
NNNN
P59 MV104 YT2_ S02_ P59 nvoYTS02p059 SNVT_count_f (51) ADI 28 0133
NNNN
P60 MV105 YT2_ S02_ P60 nvoYTS02p060 SNVT_count_f (51) ADI 29 0134
NNNN
P61 MV106 YT2_ S02_ P61 nvoYTS02p061 SNVT_count_f (51) ADI 30 0135
NNNN
P62 MV107 YT2_ S02_ P62 nvoYTS02p062 SNVT_count_f (51) ADI 31 0136
NNNN
P63 MV108 YT2_ S02_ P63 nvoYTS02p063 SNVT_count_f (51) ADI 32 0137
NNNN
P64 MV109 YT2_ S02_ P64 nvoYTS02p064 SNVT_count_f (51) ADI 33 0138
NNNN
P65 MV110 YT2_ S02_ P65 nvoYTS02p065 SNVT_count_f (51) ADI 34 0139
NNNN
P66 AV130 YT2_ S02_ P66 nvoYTS02p066 SNVT_count_f (51) ADF 73 0140
NNNN
P67 AV131 YT2_ S02_ P67 nvoYTS02p067 SNVT_count_f (51) ADF 74 0141
NNNN
P68 AV132 YT2_ S02_ P68 nvoYTS02p068 SNVT_count_f (51) ADF 75 0142
NNNN
P69 AV133 YT2_ S02_ P69 nvoYTS02p069 SNVT_count_f (51) ADF 76 0143
NNNN
P70 AV134 YT2_ S02_ P70 nvoYTS02p070 SNVT_count_f (51) ADF 77 0144
NNNN
P71 AV135 YT2_ S02_ P71 nvoYTS02p071 SNVT_count_f (51) ADF 78 0145
NNNN
P72 AV136 YT2_ S02_ P72 nvoYTS02p072 SNVT_count_f (51) ADF 79 0146
NNNN
P73 AV137 YT2_ S02_ P73 nvoYTS02p073 SNVT_count_f (51) ADF 80 0147
NNNN
P74 AV138 YT2_ S02_ P74 nvoYTS02p074 SNVT_count_f (51) ADF 81 0148
NNNN
P75 AV139 YT2_ S02_ P75 nvoYTS02p075 SNVT_count_f (51) ADF 82 0149
NNNN
P76 AV140 YT2_ S02_ P76 nvoYTS02p076 SNVT_count_f (51) ADF 83 0150
NNNN
P77 AV141 YT2_ S02_ P77 nvoYTS02p077 SNVT_count_f (51) ADF 84 0151
NNNN
P78 AV142 YT2_ S02_ P78 nvoYTS02p078 SNVT_count_f (51) ADF 85 0152
NNNN
P79 AV143 YT2_ S02_ P79 nvoYTS02p079 SNVT_count_f (51) ADF 86 0153
NNNN
P80 BV125 YT2_ S02_ P80 nvoYTS02p080 SNVT_switch (95)
BD 54 0185
NNNN
P81 BV126 YT2_ S02_ P81 nvoYTS02p081 SNVT_switch (95)
BD 55 0186
NNNN
P82 BV127 YT2_ S02_ P82 nvoYTS02p082 SNVT_switch (95)
BD 56 0187
NNNN
P83 BV128 YT2_ S02_ P83 nvoYTS02p083 SNVT_switch (95)
BD 57 0188
NNNN
P84 BV129
YT2_ S02_ P84
nvoYTS02p084 SNVT_switch (95)
BD 58
0189
N/A
0/1 0/1 Units [0=Imperial, 1=Metric] NSSS
1
2
3
4
5
6
7
8
9
10
BACnet engineering units shown with an Asterisk (*) will be assigned a BACnet engineering unit type of 95 - No Units.
Status codes: Special display characters such as ( ) [ ] { } / \ % < > are not compatible with eLink N2 formats. Substitute text strings "-", PCT, GTN will be used. String lengths are limited to 60 total
characters, including spaces.
LON SNVTs used: SNVT_count_f (51) and SNVT_switch (95). Must use LON eLink.
Modbus scaling factors indicated in
bold
with an asterisk (*) are user configurable by a field technician, if necessary. All Modbus values are of the type SIGNED with the exception of the user configurable
values that are all UNSIGNED. Modbus function types supported: ENG P03-P06 = Types 03, 06, 16; ENG P07-P10 = 01, 03, 05, 06, 15, 16; ENG P36-P55 & P80-84 = 01, 02, 03
Eng
Page
Ref
BACnet
Object
Typ/Ins
BACnet Object
Name
LON Profile
Name
LON SNVT Type
N2
Metasys
Engineering
Units
Point List Code: S = Standard O = Optional N = Not Available
NOTES
Modbus
Scroll BAS(ISN)
Johnson Controls, Inc.
Subject to change without notice.
5 of 6