LOGICA DI RISCALDAMENTO CON RE-
SISTENZE ELETTRICHE
Il sistema MP 2000 controlla la temperatura ambiente
utilizzando un sensore posto sulla ripresa aria dellunità. I
valori si riferiscono ai Set di fabbrica, essi possono essere
modificati a secondo delle esigenze dellimpianto, dopo
aver inserito la password.
Fig. 50
I set sono i seguenti:
xK Setpoint temperature (22
°C)
Setpoint del valore di temperatura media
desiderata.
xdz5 Step heater 1 Stage On (0,6
°C)
Gradino di attivazione del primo stadio di
riscaldamento.
xD5 Step heater 1 Differential (0,4
°C)
Differenziale di temperatura del primo sta-
dio di riscaldamento.
xdz6 Step heater 2 Stage On (1
°C)
Gradino di attivazione del secondo stadio di
riscaldamento.
Se è abilitata la funzione "Binary" viene
disinserito il primo stadio di riscaldamento.
xD6 Step heater 2 Differential (0,6
°C)
Differenziale di temperatura del secondo
stadio di riscaldamento.
Se è abilitata la funzione "Binary" viene
reinserito il primo stadio di riscaldamento.
xdz7 Step heater Binary Stage On (1,5
°C)
Gradino di attivazione per entrambi gli stadi
di riscaldamento.
XD7 Step heater Binary Differential (0,9
°C)
Differenziale di temperatura che disinserisce
MP2000 AIR CONDITIONERS
Software per condizionatori d'aria EPROM CZX....
Software for air conditioners
(°C) x
22
xK
0
10÷0V
0÷10V
10 (V)
2120191817
xdz5
xPs2
xPe2
xdz6
xdz7
xdzL1
xL.Alarm
xY0
xY0
off
on
off
on
off
on
Dehumid.
Limit
Heater 2
xD6
off
on
Binary
xD7
off
on
Heater 1
xD5
xDL1
0,5 0,5
HEATING LOGIC WITH ELECTRIC HEAT-
ERS
The MP 2000 system controls room temperature by means
of a sensor located on the air intake of the unit.
The values refer to the factory settings and may be modified
according to plant requirements, after inserting the pass-
word.
The sets are the following:
xK Set point temperature (22
°
C)
Set point of the desired average tempera-
ture value.
xdz5 Step heater 1 Stage On (0.6
°
C)
Activation step of the first heating stage.
xD5 Step heater 1 Differential (0.4
°
C)
Temperature differential of the first heating
stage.
xdz6 Step heater 2 Stage On (1
°
C)
Activation step of the second heating stage.
If the "Binary" function is enabled, the first
heating stage is disconnected.
xD6 Step heater 2 Differential (0.6
°
C)
Temperature differential of the second heat-
ing stage.
If the "Binary" function is activated, the first
heating stage is activated.
xdz7 Step heater Binary Stage On (1.5
°
C)
Activation step of both heating stages.
XD7 Step heater Binary Differential (0.9
°
C)
Temperature differential due to the stop of
the first heating stage and leaves the second
one ON.
Note: the "Binary" function also allows the