RC GROUP - 149_ItEn.0102
1. Connettore per alimentazione 24Vac o 24Vdc (+10% /
-15%) 50/60 Hz - 15VA.
2. LED giallo indicante presenza tensione.
3. Connettore a morsetti estraibili per rete LAN.
4. Connettore telefonico per connessione terminale.
5. Connettore per scheda indirizzamento "ADDR" fornita
di serie.
Scheda indirizzamento+orologio "ADDR+CK" a richie-
sta.
6. Uscite analogiche 0÷10Vdc optoisolate
Y: Uscite analogiche 1 e 2, carico max 1k (10mA).
VG1: Alimentazione esterna per uscite analogiche
(24Vac o 24Vdc).
VG0: Riferimento per lalimentazione e per il segna-
le delle uscite analogiche Y0 e Y1.
7. Ingressi digitali optoisolati:
ID11-230Vac, ID12-230Vac: Ingressi digitali 11 e 12
per segnali a 230Vac.
ID11-24Vac, ID12-24Vac: Ingressi digitali 11 e 12 per
segnali a 24Vac o 24Vdc ±15%.
ID11-R, ID12-R: riferimento comune per ingressi di-
gitali ID11 e ID12.
Evitare di portare segnali a 230Vac sul morsetto per
24Vac, pena danneggiamento della scheda stessa.
8. Uscite digitali 2500VA - 250Vac - 10A resistivi:
NO: Contatto normalmente aperto.
NC: Contatto normalmente chiuso.
C: Contatto comune.
9. Uscite digitali 250Vac - 10A resistivi:
NO: Contatto normalmente aperto.
C: Contatto comune per il contatto.
10. Ingressi digitali optoisolati 24Vac o 24Vdc (10mA):
ID: Ingressi digitali 1÷10.
IDCM1: Riferimento comune ingressi digitali 1÷5.
IDCM2: Riferimento comune ingressi digitali 6÷10.
11. Ingressi analogici:
B: Ingresso analogico 1÷6.
AVSS: riferimento comune degli ingressi analogici B.
Da B1 a B4 accettano sonde NTC. B5 e B6 sono
selezionabili per sonde con segnale 0÷1Vdc o
4÷20mA tramite ponticelli.
12. Ingressi analogici:
B: Ingresso analogico 7 e 8.
+24Vdc: Alimentazione sonde attive e sensori di pres-
sione 4÷20mA (max 80mA).
Selezionabili per sonde con segnale 0÷1Vdc o
4÷20mA tramite ponticelli.
13. Scheda porta seriale RS485 optoisolata (a richiesta).
14. Ponticelli per impostazioni:
J8 in posizione 2-3.
J9 in posizione 2-3.
J14 selezione dellingresso analogico B5
1-2=4÷20mA, 2-3=0÷1Vdc.
J15 selezione dellingresso analogico B6
1-2=4÷20mA, 2-3=0÷1Vdc.
J28 selezione dellingresso analogico B7
1-2=4÷20mA, 2-3=0÷1Vdc.
J29 selezione dellingresso analogico B8
1-2=4÷20mA, 2-3=0÷1Vdc.
15. Eprom contenente programma applicativo.
16. Fusibile 250Vac, 2A ritardato (2TA).
1. 24Vac or 24Vdc power supply connector (+10% / -15%)
50/60 Hz - 15VA.
2. Yellow LED for voltage presence indication.
3. Plug-in connector for LAN network.
4. Telephone-type connector for teminal connection.
5. Connector for address card "ADDR" (standardly sup-
plied).
On request address+clock card "ADDR+CK".
6. Analog outputs 0
÷
10Vdc opto-insulated
Y: Analog outputs 1 and 2, max load 1k
(10mA).
VG1: External power supply for analog outputs (24Vac
or 24Vdc).
VG0: Reference for power supply and analog outputs
signals Y0 and Y1.
7. Opto-insulated digital inputs:
ID11-230Vac, ID12-230Vac: Digital inputs no. 11
and 12 for 230Vac signals.
ID11-24Vac, ID12-24Vac: Digital inputs no. 11 and
12 for 24Vac or 24Vdc
±
15% signals.
ID11-R, ID12-R: Common references for digital in-
puts ID11 and ID12.
Never connect the 230Vac signals to the 24Vac termi-
nal; you damage the main board.
8. Digital outputs 2500VA - 250Vac - 10A resistive load:
NO: Normally open contact.
NC: Normally closed contact.
C: Common contact.
9. Digital outputs 250Vac - 10A resistive load:
NO: Normally open contact.
C: Common contact.
10. Opto-insulated digital inputs 24Vac or 24Vdc (10mA):
ID: Digital inputs 1
÷
10.
IDCM1: Common reference for digital inputs 1
÷
5.
IDCM2: Common reference for digital inputs 6
÷
10.
11. Analog inputs:
B: Analogue input 1
÷
6.
AVSS: Common reference of the analogue inputs B.
From B1 to B4 preset to accept NTC sensors. B5 and
B6 selectable to accept either 4
÷
20mA or 0
÷
1Vdc
signals through jumper.
12. Analog inputs:
B: Analogue input 7 and 8.
+24Vdc: Active probes and pressure probes 4
÷
20mA
feeding (max 80 mA).
Selectable to accept either 4
÷
20mA or 0
÷
1Vdc sig-
nals, through jumper.
13. Opto-insulated RS485 serial port (optional).
14. Jumpers for settings:
J8 in position 2-3.
J9 in position 2-3.
J14 - B5 analog input selection
1-2=4
÷
20mA, 2-3=0
÷
1Vdc.
J15 - B6 analog input selection
1-2=4
÷
20mA, 2-3=0
÷
1Vdc.
J28 - B7 analog input selection
1-2=4
÷
20mA, 2-3=0
÷
1Vdc.
J29 - B8 analog input selection
1-2=4
÷
20mA, 2-3=0
÷
1Vdc.
15. Eprom with application program.
16. 250Vac fuse, 2A delayed (2TA).
MP2000 AIR CONDITIONERS
Sistema di controllo a microprocessore per condizionatori d'aria •
Air conditioners microprocessor control system

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RC GROUP MP2000 and is the answer not in the manual?

RC GROUP MP2000 Specifications

General IconGeneral
BrandRC GROUP
ModelMP2000
CategoryController
LanguageEnglish