2916456
32
GB
Maintenance
Photocell (Fig. 33)
Clean the glass cover from any dust that may have accumulated.
Photocell 1) is held in position by a pressure fit and can therefore
be removed by pulling it outward forcefully.
Flame inspection window (Fig. 34)
Clean the glass whenever necessary.
Flexible hoses
Check to make sure that the flexible hoses are still in good con-
dition and that they are not crushed or otherwise deformed.
Check periodically the flexible pipes conditions. Using kerosene,
they have to be replaced at least every 2 years.
Fuel tank
Approximately every 5 years, or whenever necessary, suck any
water or other impurities present on the bottom of the tank using
a separate pump.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics in-
tact, especially the flue gas temperature and combustion cham-
ber pressure.
Fuel pump and/or couplings replacement
In conformity with (Fig. 35).
Fig. 33
D708
Fig. 34
D709
Fig. 35
D1108

Table of Contents

Related product manuals