Appendix - Accessories
• Radio disturbance protection kit
If the burner is installed in places particularly subject to radio dis-
turbance (emission of signals exceeding 10 V/m) owing to the
presence of an INVERTER, or in applications where the length of
the thermostat connections exceeds 20 metres, a protection kit is
available as an interface between the control box and the burner.
• Degassing unit
It may occur that a certain amount of air is contained in the fuel
sucked up by the pump. This air may originate from the fuel itself
as a consequence of depressurisation or air leaking past imper-
fect seals.
In double-pipe systems, the air returns to the tank from the return
pipe; in single-pipe systems, the air remains in circulation causing
pressure variations in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the
burner in single-pipe installations.
Degassing units are provided in two versions:
Code 20034277 without filter
Code 20034281 with filter
For burner deliveries higher than 80 kg/h, install two parallel de-
gassing units.
A Appendix - Accessories
Burner Code
RL 70 - RL 100 - RL 130 3010386
Degassing unit characteristics
- Burner delivery : max. 80 kg/h
- Fuel pressure : max. 0.7 bar
- Ambient temperature : max. 50 °C (without filter)
- Ambient temperature : max. 40 °C (with filter)
- Fuel temperature : max. 50 °C (without filter)
- Fuel temperature : max. 40 °C (with filter)
- Attachment connectors : 1/4 inch