2.3 List of Parameters in Initialize Code 0 (Cod = 0)
(1) SL1 (Input type selection)
Conduct the setting so that it matches the instrument specification (input type). If the setting
is changed, always check all of the set values (SV setting mode, parameter setting mode).
Factory set value varies depending on the input type.
Set value Input type
0000 K
0001 J
0010 L
0011 E
0100 N
0 1 1 1 R TC input *1
1000 S
1001 B *4
1 0 1 0 W5Re/W26Re *4
1011 PL II
0101 T
0110 U
1100
Pt100 (JIS/IEC)
RTD input *1
1101
JPt100 (JIS)
1 1 1 0 0 to 5 V DC
1 1 1 0 0 to 10 V DC *2 Voltage input *1
1 1 1 1 1 to 5 V DC
1 1 1 0 0 to 20 mA DC Current input *1, *3
1 1 1 1 4 to 20 mA DC
*1 No input type (TC/RTD input to voltage/current input or voltage/current input to TC/RTD input)
cannot be changed.
*2 To be fixed to 1110 for the 0 to 10 V DC (Z-1010 specification). No input type cannot be changed
as the hardware differs.
*3 For the current input specification, a resistor of 250 must be connected between the input
terminals.
*4 Can’t be selected for the instrument with the modbus communication specification (Z-1021
specification).