2. SETTING
IMCB04-E9
10
(4) SL4 (First alarm [ALM1] type selection, hold action selection)
The following instrument is set to 0000.
Instrument without the first alarm (ALM1) output.
Instrument of the SV alarm or control loop break alarm (LBA) is used as the first alarm
(ALM1).
Factory set value varies depending on the instrument specification.
Set value Description
0 0 0 First alarm (ALM1) not provided
0 0 1 Deviation high alarm
0 1 0 Deviation high/low alarm
0 1 1 Process high alarm First alarm (ALM1) type selection
1 0 1 Deviation low alarm
1 1 0 Band alarm
1 1 1 Process low alarm
0 Without alarm hold action First alarm (ALM1) hold action selection
1 With alarm hold action
(5) SL5 (Second alarm [ALM2] type selection, hold action selection)
The following instrument is set to 0000.
Instrument without the second alarm (ALM2) output.
Instrument of the SV alarm, heater break alarm (HBA) or control loop break alarm (LBA)
is used as the second alarm (ALM2).
Instrument with the Z-168 specification.
Factory set value varies depending on the instrument specification.
Set value Description
0 0 0 Second alarm (ALM2) not
0 0 1 Deviation high alarm
0 1 0 Deviation high/low alarm
0 1 1 Process high alarm Second alarm (ALM2) type selection
1 0 1 Deviation low alarm
1 1 0 Band alarm
1 1 1 Process low alarm
0 Without alarm hold action Second alarm (ALM2) hold action selection
1 With alarm hold action