2. SETTING
IMCB04-E9
10
(4) SL4 (First alarm [ALM1] type selection, hold action selection)
The following instrument is set to 0000.
• Instrument without the first alarm (ALM1) output.
• Instrument of the SV alarm or control loop break alarm (LBA) is used as the first alarm
(ALM1).
Factory set value varies depending on the instrument specification.
Set value Description
0 0 0 First alarm (ALM1) not provided
0 0 1 Deviation high alarm
0 1 0 Deviation high/low alarm
0 1 1 Process high alarm First alarm (ALM1) type selection
1 0 1 Deviation low alarm
1 1 0 Band alarm
1 1 1 Process low alarm
0 Without alarm hold action First alarm (ALM1) hold action selection
1 With alarm hold action
(5) SL5 (Second alarm [ALM2] type selection, hold action selection)
The following instrument is set to 0000.
• Instrument without the second alarm (ALM2) output.
• Instrument of the SV alarm, heater break alarm (HBA) or control loop break alarm (LBA)
is used as the second alarm (ALM2).
• Instrument with the Z-168 specification.
Factory set value varies depending on the instrument specification.
Set value Description
0 0 0 Second alarm (ALM2) not
0 0 1 Deviation high alarm
0 1 0 Deviation high/low alarm
0 1 1 Process high alarm Second alarm (ALM2) type selection
1 0 1 Deviation low alarm
1 1 0 Band alarm
1 1 1 Process low alarm
0 Without alarm hold action Second alarm (ALM2) hold action selection
1 With alarm hold action